Permit: T03CM02039

Parcel: 10603167C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/30/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) ABS DWV THRU ROOF-OK 2) COPPER-OK 3) OK TO COVER WALLS
07/25/2003 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) NOBODY ON JOB 2) 2" WYE INSTALLED IN WRONG DIRECTION
07/24/2003 PLUMBING - INTERMEDIATE Not ready for Inspection
07/02/2003 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) CORRECTIONS MADE-OK 2) OK TO COVER ALL AREAS
07/01/2003 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) PLEASE ADD ROUGH/SOIL 03005 TO PERMIT 2) NOT INSTALLED PER PLAN-PLAN CALLS FOR BELL AND SPIGOT CAST IRON-INSTALLED IS ABS 3) A BLAKE TEE IS NOT PERMITTED BELOW GRADE. BLAKE TEE IS NOT PERMITTED ON IT'S BACK PLEASE READ THE LISTING FOR THIS FITTING 316.1.5 IS5 94 UPC 4) OK TO BACKFILL (WITH ARCHITECT APPROVAL OF NAT'L) ALL AREAS EXCEPT TREST TEES MAY BE COVERED 5) WATER TEST ONE RISER TO TEN FEET-OK