Permit: T03CM02039

Parcel: 10603167C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/22/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/21/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) WORK INCOMPLETE BUT IN PROGRESS 2) ONE SIDE DRYWALL-OK
08/15/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1/2 REAR WALLS OK.
08/14/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*/1) BACK TO BACK BOXES MUST BE CONNECTED WITH A CHASE NIPPLE - OR? .2) THE ELECTRICAL PLANS DO NOT MENTION THE USE OF METAL CLAD CABLE. THE ENGINEER OF RECORD MUST SUBMIT A LETTER ALLOWING THE USE OF M/C CABLE. 3) ALARM AND COMMUNICATION CONDUITS AND CABLES ARE MISSING.