Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2003 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FOR SHEET ROCK |
| 07/01/2003 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SEAL JOINTS ON MEETAL DUCT 2) INSULATE SIDE WALL REGISTER BOXES 2ND FLOOR 3) PROVIDE SECONDARY DRAIN OR CAP OUTLET ON DRAIN PAN 4) PROVIDE FRAMING FOR SUPPLY BOXES IN KITCHEN, 2ND FLOOR 5) PROVIDE BUSHINGS WHERE REFER LINES PENETRATE THE FAN COIL 6) 1ST FLOOR CONDENSATE DRAIN NOT SLOPED CORRECTLY. PROVIDE FRAMING AROUND CEILING BOXES 1ST FLOOR CONNECT DUCT TO EXHAUST FAN 1ST FLOOR |