Permit: T03CM02036

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/02/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK FINAL
09/29/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) AN APPROVED CONNECTOR IS NEEDED FOR NM CABLE AT HOODS 2) ROOF: TIGHTEN LOOSE SEAL TITE FITTINGS 3) CORRECTLY IDENTIFY UNDERGROUND CONDUCTORS AT DISCONNECTS 4) FINISH PREVIOUS INSPECTIONS #2, 6 AND 5
09/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) GROUND FIXTURE SUPPORTS 2) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 3) INSTALL HOODS 4) APPROVED EXTENDER RINGS ARE NEEDED WHERE BOX IN MORE THAN 1/4" FROM BOX TO SURFACE OR AT COMBUSTIBLES 370.20 5) ARCFAULT BREAKERS CALLED FOR ON PLANS-NOT INSTALLED 6) MAINTAIN WORKING CLEARANCE AT SERVICE METERS 7) INSTALL FRONT LIGHTS 8) FINISH ELECTRICAL ON ROOF