Permit: T03CM02031

Parcel: 106070980

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/30/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/APPROVED
08/11/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
07/26/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection. Item #1 and 2 not corrected. #3 ? data plate covered by duct work
07/02/2004 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*/ 1) DUCT SMOKE DETECTORS - IMC 606.2.1 - SMOKE DETECTORS LOCATED IN RETURNS - NFPA REFERS TO IMC FOR PROPER LOCATION. 2) NEED COVER FOR FLEX DUCT CONNECTOR ON RETURN AIR SYSTEM. 3) DATA PLATE FOR UNIT 3/4 COVERED - NO INFO CAN BE ACCESSED CONCERNING VOLTAGE, AMPERAGE, MOD/SER #'S. PLEASE SECURE DUPLICAT.
06/02/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio/ THE ISSUE OF ACCESS HAS STILL NOT BEEN ADDRESSED. THIS ARCHITECT NEEDS TO PROVIDE FOR ACCESS THRU REAR SCREEN OF BLDG. WEST SIDE OF BLDG ACCESSES THE WEST EXHAUST BLWR AND THE OTHER HALF OF COMB. PKG UNIT. PERM LADDER ON REAR IS GOOD FOR ONLY HALF OF EQUIPMENT. THIS ARCH NEEDS TO DEAL WITH THIS ACCESS PROBLEM FOR FINAL.