Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/APPROVED | |
| 08/11/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/26/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection. Item #1 and 2 not corrected. #3 ? data plate covered by duct work |
|
| 07/02/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/ 1) DUCT SMOKE DETECTORS - IMC 606.2.1 - SMOKE DETECTORS LOCATED IN RETURNS - NFPA REFERS TO IMC FOR PROPER LOCATION. 2) NEED COVER FOR FLEX DUCT CONNECTOR ON RETURN AIR SYSTEM. 3) DATA PLATE FOR UNIT 3/4 COVERED - NO INFO CAN BE ACCESSED CONCERNING VOLTAGE, AMPERAGE, MOD/SER #'S. PLEASE SECURE DUPLICAT. | |
| 06/02/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio/ THE ISSUE OF ACCESS HAS STILL NOT BEEN ADDRESSED. THIS ARCHITECT NEEDS TO PROVIDE FOR ACCESS THRU REAR SCREEN OF BLDG. WEST SIDE OF BLDG ACCESSES THE WEST EXHAUST BLWR AND THE OTHER HALF OF COMB. PKG UNIT. PERM LADDER ON REAR IS GOOD FOR ONLY HALF OF EQUIPMENT. THIS ARCH NEEDS TO DEAL WITH THIS ACCESS PROBLEM FOR FINAL. |