Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) C OF O | |
| 07/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THE SERVICE DISCONNECT FOR A/C UNIT ON ROOF MUST BE INSTALLED IN A LOCATION WHERE THERE IS 3' OF CLEARANCE IN FRONT OF ALL THE WAY DOWN TO GRADE 99 NEC 110-26. ALSO DOOR MUST ALWAYS OPEN FREELY 2) ELECTRICAL ROOM LOCKED WHERE SERVICE DISCONNECT LOCATED. COULD NOT MAKE AN AM INSPECTION THIS TIME |
|
| 06/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) RECEPTACLE UNDER PANEL MP TO BE FINISHED. 2) INSTALL PROPER PANEL SCEDULE IN PANEL MP. 3) PANEL SCHEDULE CUT OUT OF APPROVED PLANS? NEED TO SEE APPROVED ONE. 4) PLAN SHOWS AC UNITS 1 & 2 TO COME OUT OF PANEL M-P. HOWEVER THEY ARE NOT ON PANEL. 5) OPEN TIME CLOCK - SHOULD NOT BE PAINTED CLOSED, LABEL WHAT IT CONTROLS. 6) WEST NIGHT LIGHT - ONE NOT WORKING - LAMP . 7) NEW 200 A FUSED DISCONNECT AT FEED TO BE PERMAMNETY LABELED CAFETERIA PANEL MP, INSTALL REJECT PINS. 8) GROUNDING SYSTEM AS SHOWN ON PLAN NOT INSTALLED. 9) NO ACCESS TO ROOF - hOW ARE UNITS FED? WILL NEED AR EVISION IF DIFFERANT THAN PLAN. 10) NEED TO INSPECT DISCONNECT MP TIE INTO GUTTER. HAVE ELECT OPEN TO INSPECT. |