Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM02004
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
08/01/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*/ 1) M/C CABLE, CONDUIT AND BOXES TO BE SUPPORTED AS PER 300-11 AT BOTH ENDS 2) M/C CABLE NOT TO LAY ON CEILING GRID 3) JUNCTION BOXES TO BE GROUNDED 4) PLEASE PRESENT ELECTRIC CONTACT BETWEEN CONDUIT AND COPPER PIPING 5) SEAL UNUSED OPENINGS IN JUNCTION BOX 6) CONDUIT NOT TO BE SUPPORTED OFF OF CONDUIT 7) SUPPORT WIRE NEEDED ON RECEPTACLE BOX IN CELL |