Permit: T03CM02004

Parcel: 13348128A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM02004

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
08/01/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) M/C CABLE, CONDUIT AND BOXES TO BE SUPPORTED AS PER 300-11 AT BOTH ENDS 2) M/C CABLE NOT TO LAY ON CEILING GRID 3) JUNCTION BOXES TO BE GROUNDED 4) PLEASE PRESENT ELECTRIC CONTACT BETWEEN CONDUIT AND COPPER PIPING 5) SEAL UNUSED OPENINGS IN JUNCTION BOX 6) CONDUIT NOT TO BE SUPPORTED OFF OF CONDUIT 7) SUPPORT WIRE NEEDED ON RECEPTACLE BOX IN CELL