Permit: T03CM01986

Parcel: 128102940

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/16/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) OK C OF O
07/17/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK FOR TEMP C OF O
07/16/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) COMPLETE INSULATING REFER LINE. 2) LABEL EQUIPMENT. 3) PROVIDE ACCESS TO FILTERS. 4) PROVIDE OUTSIDE AIR TO FAN COILS. 5) RELOCATE SECONDARY DRAIN IN SERVER ROOM. 6) FINISH CONNECTING DIFFUSERS.