Permit: T03CM01986

Parcel: 128102940

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/16/2003 MECHANICAL - ABOVE CEILING Approved
07/08/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000* INSPECTED LOW PRESSURE DUCT AND DIFFUSERS. O.K. FOR CEILING TILES IN ALL AREAS EXCEPT AROUND VAV BOXES & FAN COILS. STILL NEED TO SEE SERVER ROOMS.
06/30/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) SUSPENDED ROUGH DUCT. OK TO PROCEED. PRIMARY CONDENSATE DRAINS ARE OK. SECONDARY NEEDS WORK