Permit: T03CM01929

Parcel: 110033710

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T03CM01929

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
10/30/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) CLIP PORCH LEDGER TO RESIST PULL AWAY 2) 2ND FLOOR BOTTOM PLATES REQUIRED MORE NAILING 3) FRONT P3 SHEAR REQUIRES 3' ON CENTER EDGE NAILING 4) GABLE END BRACING REQUIRED FRONT AND REAR 5) DOUBLE TOP PLATES MUST BE STRAPPED INSIDE AND OUTSIDE WHEN NOT LAPPED