Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM01927
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2003 | MECHANICAL - ABOVE CEILING | Approved | ||
05/27/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | 1) NOTE: FOR FINAL MECHANICAL HAVE ROOF ACCESS READY. WILL CHECK TO SEE ALL EXISTING ROOF TOP UNITS ARE PROPERLY FUSED, ALL CONDENSATE DRAINS CONNECTED TO PROPER TEMINATION POINT, ETC... 2) ABOVE CEILING HAVE EXISTING FIRE DAMPERS INTEGRITY (GENERAL CONDITION) BEEN CHECKED ?? 3) MIGHT WANT TO BE CERTAIN THAT THEY WILL DROP CLOSED IF NECESSARY |