Permit: T03CM01927

Parcel: 113052560

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM01927

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
05/13/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*SUBJECT TO THE FOLLOWING REQUIREMENT. PLAN ELECTRICAL SPEC'S REQUIRE THE USE OF EMT CONDUIT IN WALLS. THE USE OF MC CABLE IS NOT APPROVED.
PLEASE SUBMIT A LETTER ISSUED BY THE ARCHITECT/ENGINEER OF RECORD GIVING EXPRESS CONSENT OF MC CABLE ON THE PROJECT. SUBMIT LETTER TO CITY OF TUCSON PLAN REVIEW FOR REVIEW & APPROVAL AND INCLUSION OF LETTER TO FOR THE PUBLIC RECORD.