Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/12/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/11/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 5KW AUX. HT. STRIPS - MAX. FUSE SIZE 30 AMPS! --- FUSES AT 35??? WHY?? READ YOUR DATA PLATE AS IT'S MARKED. PLEASE CORRECT. THANK YOU. |
| 08/08/2003 |
MECHANICAL - FINAL |
|
Denied |
RE-FEE DUE |
| 08/07/2003 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1ST FLR. CONDENSATE DRAINS - INCOMPLETE. ELEC. DATA PLATE - A/H? |
| 08/06/2003 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ NOTE: BE SURE ELEC DATA PLATE - 1ST FLOOR APTS. 1) MARK PROPER AUX. HEAT STRIP IN VERTICAL AIR HANDLERS SO PROPER FUSE SIZE CAN BE VERIFIED. 2) LEAVE REMOTE CONDENSORS PROPERLY FUSED. |