Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM01922
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
08/11/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 5KW AUX. HT. STRIPS - MAX. FUSE SIZE 30 AMPS! --- FUSES AT 35??? WHY?? READ YOUR DATA PLATE AS IT'S MARKED. PLEASE CORRECT. THANK YOU. | |
08/08/2003 | MECHANICAL - FINAL | Denied | RE-FEE DUE | |
08/07/2003 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1ST FLR. CONDENSATE DRAINS - INCOMPLETE. ELEC. DATA PLATE - A/H? | |
08/06/2003 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ NOTE: BE SURE ELEC DATA PLATE - 1ST FLOOR APTS. 1) MARK PROPER AUX. HEAT STRIP IN VERTICAL AIR HANDLERS SO PROPER FUSE SIZE CAN BE VERIFIED. 2) LEAVE REMOTE CONDENSORS PROPERLY FUSED. |