Permit: T03CM01922

Parcel: 117030290

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM01922

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/07/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
08/06/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0215* THE FOLLOWING ITEMS NEED CORRECTION. 1. LIGHTING FIXTURES IN CLOSETS MUST HAVE LENS WHICH COVER THE OPENING INTO THE CAN AND LIGHT BULB. 2) APARTMENT PANEL INDEXES AND APT. NUMBER ON PANEL COVERS. 3) A/C DUCT MUST HAVE GROUND STRAPS INSTALLED TO BRIDGE ACROSS FAU AND ATTIC DUCT AT THE RUBBER BAFFLE. 4) THE TWO 4'' CONDUITS FOR SERVICE CONDUCTORS MUST BE BONDED TO THE SERVICE PANEL GROUND. USE BONDING BUSHINGS. 5. TIGHTEN CONNECTORS AND COUPLINGS ON EMT ??