Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/08/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/07/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/06/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215* THE FOLLOWING ITEMS NEED CORRECTION. 1. LIGHTING FIXTURES IN CLOSETS MUST HAVE LENS WHICH COVER THE OPENING INTO THE CAN AND LIGHT BULB. 2) APARTMENT PANEL INDEXES AND APT. NUMBER ON PANEL COVERS. 3) A/C DUCT MUST HAVE GROUND STRAPS INSTALLED TO BRIDGE ACROSS FAU AND ATTIC DUCT AT THE RUBBER BAFFLE. 4) THE TWO 4'' CONDUITS FOR SERVICE CONDUCTORS MUST BE BONDED TO THE SERVICE PANEL GROUND. USE BONDING BUSHINGS. 5. TIGHTEN CONNECTORS AND COUPLINGS ON EMT ?? |