Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM01909
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK FINAL | |
06/16/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) APPROVED EXTENDER RINGS ARE NEEDED WHERE BOXES ARE MORE THAN 1/4" TO SURFACE 370.20 2) FILL UNUSED OPENING IN PANEL BOTTOM AND AT A/C #1 3) COVER TO BE WHEATHER PROOF WHEN PLUGGED IN 410357 4) PLEASE REMOVE EXPOSED CONDUCTORS BACK TO LAST SAGE JUNCTION BOX 5) SUPPORT CONDUIT AND TIGHTEN SEAL TIGHT FITTING FOR A/C 6) PLEASE OPEN EXHAUST FAN TO VERIFY DISCONNECTING MEANS |