Permit: T03CM01904

Parcel: 133553300


Addresses:

250 S VOZACK LN


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM01904

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/OK FOR FINAL C/O
12/06/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/SUPPORT ALL WIRING ABOVE CEILING AS PER N.E.C. PROVIDE POWER TO THE DUCT SMOKE DETECTOR & INSTALL THE PLASTIC COVER. RECALL FOR INSPECTION
09/02/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/DENIED
RECALL FOR INSPECATION AFTER FINE DAMPERS & DUCT SMOKE DETECTOR ARE OPERATIONAL
08/20/2004 MECHANICAL - FINAL Denied IVRS - Inspection :EXTEND WATER HEATER VENT CONNECTOR INTO DOUBLE WALL & PROVIDE MIN 3 SCREWS IN CONNECTION
MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY
DISCONNECT IS BLOCKING ACCESS TO SERVICE PANEL ON A/C UNIT
PROVIDE ROOF JACKS AT CONDENSATE PENETRATIONS THRU THE ROOF.
ADEQUATELY SUPPORT PVC ON ROOF
CONDENSATE DRAIN HAS BACKPITCH
ANGLE IRON ON FIRE DAMPER NOT FLUSH WITH WALL ABOVE SINK
SECURE THE DRYER VENTS ON THE ROOF
FINISH CONNECTING DUCT SMOKE DETECTORS