Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM01904
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/OK FOR FINAL C/O | |
12/06/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/SUPPORT ALL WIRING ABOVE CEILING AS PER N.E.C. PROVIDE POWER TO THE DUCT SMOKE DETECTOR & INSTALL THE PLASTIC COVER. RECALL FOR INSPECTION |
|
09/02/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DENIED RECALL FOR INSPECATION AFTER FINE DAMPERS & DUCT SMOKE DETECTOR ARE OPERATIONAL |
|
08/20/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection :EXTEND WATER HEATER VENT CONNECTOR INTO DOUBLE WALL & PROVIDE MIN 3 SCREWS IN CONNECTION MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY DISCONNECT IS BLOCKING ACCESS TO SERVICE PANEL ON A/C UNIT PROVIDE ROOF JACKS AT CONDENSATE PENETRATIONS THRU THE ROOF. ADEQUATELY SUPPORT PVC ON ROOF CONDENSATE DRAIN HAS BACKPITCH ANGLE IRON ON FIRE DAMPER NOT FLUSH WITH WALL ABOVE SINK SECURE THE DRYER VENTS ON THE ROOF FINISH CONNECTING DUCT SMOKE DETECTORS |