Permit: T03CM01904

Parcel: 133553300


Addresses:

250 S VOZACK LN


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM01904

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/07/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/06/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) OK FOR TEMP C OF O WITH BOND POSTED
2) NEED PANEL FEEDER PROPERLY PROTECTED AT PANEL ENTRY
3) INSTALL ANTI OX. PASTE AT ALL ALUMINUM TERMINATIONS (AT HEAT PUMP FUSED PULLOUTS)
4) VERIFY W/MECH CONTRACTOR UNIT FUSING ? WIRE GOOD FOR 50 AMPS
08/20/2004 ELECTRIC - FINAL Not ready for Inspection CALL IN ALL INSPECTIONS
07/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*/ 1) SERVICE INSPECTION: TEP ENERGIZED WITHOUT CITY APPROVAL 2) TOP ENTRIES INTO 400 AMP METER COMBO PANEL BOARD NOT APPROVED. INSPECTOR VIEWS THIS AS HAZARDOUS AND AREA SHOULD BE DEDICATED TO UTILITY 3) WILL NEED COMPLETE ACUURATE CITY APPROVED REVISION ON ONE LINE DIAGRAM 4) NEED SERVICE PANEL DIAGRAM