Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM01904
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/07/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/06/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) OK FOR TEMP C OF O WITH BOND POSTED 2) NEED PANEL FEEDER PROPERLY PROTECTED AT PANEL ENTRY 3) INSTALL ANTI OX. PASTE AT ALL ALUMINUM TERMINATIONS (AT HEAT PUMP FUSED PULLOUTS) 4) VERIFY W/MECH CONTRACTOR UNIT FUSING ? WIRE GOOD FOR 50 AMPS |
|
08/20/2004 | ELECTRIC - FINAL | Not ready for Inspection | CALL IN ALL INSPECTIONS | |
07/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*/ 1) SERVICE INSPECTION: TEP ENERGIZED WITHOUT CITY APPROVAL 2) TOP ENTRIES INTO 400 AMP METER COMBO PANEL BOARD NOT APPROVED. INSPECTOR VIEWS THIS AS HAZARDOUS AND AREA SHOULD BE DEDICATED TO UTILITY 3) WILL NEED COMPLETE ACUURATE CITY APPROVED REVISION ON ONE LINE DIAGRAM 4) NEED SERVICE PANEL DIAGRAM |