Permit: T03CM01903

Parcel: 11628001E

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/29/2004 FRAMING Approved IVRS - Inspection :*
03/25/2004 FRAMING Partial Approval IVRS - Inspection 0000* ROOF I, J
2 HOUR REQUIREMENT FOR ROOF CONSTRUCTION IS FOR TYPE 1A BLDG. THIS IS NOT AN AREA SEPARATION REQUIREMENT. FLOATING LIGHT WEIGHT CONCRETE DOWN TO ROOF DRAINS @ FLUSHING IS ACCEPTABLE. REF 1994 U.B.C. SEC 710.4.
FIRE RESISTIVE ROOFS MAY HAVE UNPROTECTED OPENINGS.
03/10/2004 FRAMING Partial Approval IVRS - Inspection 0000* WING I, J 1) MONOKOTE FIRE SAFING PROGRESS OK. OK TO SKIN EXTERIOR OF BUILDING. 2) STUCCO MESH PROGRESS NORTH FACE OK. 3) FIRE STOP @ MEZZ LEVEL AREA J OK TO SKIN INSIDE. 4) CONSTRUCTION OF 2 HOUR AREA SEPARATION WALL A BALL ROOM AREA OK TO CONTINUE AS DISCUSSED WITH WEITZ
03/01/2004 FRAMING Partial Approval IVRS - Inspection 0000* 1) I, J SUPER STRUCTUR A) HUNG GRIDERS OK. B) PROGRESS ON FIRE COATING OK. OK TO SKIN EAST END.
02/12/2004 FRAMING Partial Approval IVRS - Inspection 0000* P-1-I,J MONOKOTE ON STEEL ALONG LINE 24 NORTH FACE OK. OJ TO SKIN ARCHITECTURAL.
02/06/2004 FRAMING Partial Approval IVRS - Inspection 0000* 1) AREA I-J ROOF DECKS A) ALL FLAT DECKS EXCEPT SOUTH & EAST EDGE LINE YY & LINE 32.2 OK HIGH ROOF. B) PITCHED ROOF DECKS INCOMPLETE. 2) COLD FORM STEEL ATTACHMENTS TO DECKS A) AREA I COMPLETE. B) LINE QQ REQUIRES TRACK SCREWS 12"OC ALONG BOTTOM. C) PROGRESS AREA J LOOKS VERY GOOD BUT WORK IS INCOMPLETE. D) OK TO START COVERING C.F. STEEL AFTER FIRE PROOFING INSP OF STRUCTURAL STEEL.
01/29/2004 FRAMING Partial Approval IVRS - Inspection 0000* 1) SUPER STRUCTURE STEEL COMPLETE. FINAL PLATE WELDS INSP AND REINSPECTION OF DECK WHERE IT WAS LOWERED ARE BEING DONE TODAY. 2) CLIP WELDS FOR ARCHITECTURAL COLD FORM STEEL OK. 3) DECK WELDS INCOMPLETE @ ROOF AND NOT YET DONE FOR SLAB AREA @ I, H
12/17/2003 FRAMING Partial Approval IVRS - Inspection 0000* 1) UPPER ROOF DECK AREA I REQUIRES MORE WELDS PER GSN'S 7 PUDDLE WELDS REQUIRED @ ALL INTERMEDIATE SUPPORTS. 2) PARAPET WALLS REQUIRE 2 #10 SCREWS 12" OC TO FSTEN BOTTOM TRACK.
12/16/2003 FRAMING Partial Approval IVRS - Inspection 0000* 1) PERIMETER PARAPET WALL @ROOF JJ-QQ/25-30. 2) ROOF DECK WELDS JJ-QQ OK.
12/05/2003 FRAMING Partial Approval IVRS - Inspection 0000* 1) RFI 359 RECEIVED FOR REPAIR OF BRACED FRAME COLS, AREA P1-I. 2) SUPER STRUCTURE FRAMING & DECKING P-1-I & J PROGRESSING ACCEPTABLY
10/31/2003 FRAMING Partial Approval IVRS - Inspection 0000* STRUCUAL BRACED FRAMES LINES 25 REQUIRE RFI FOR CUT & REWELD AT BASE PLATES