Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/07/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 08/05/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 2) BOND BUSHING AT CONCENTRIC WITH VOLTAGE OVER 250V 250.97 3) PANEL SCHEDULE TO BE PERMANENT |
| 07/25/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
OK FOR TEMP C/O |
| 07/25/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
1) GROUND METAL BOXES FOR OUTLETS 250.148 2) FINISH ITEMS FROM PREVIOUS INSPECTION AND CALL FOR MONDAY 3) OK TEMP C OF O TI |
| 07/24/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SUPPORT CODUIT IN CEILING. 2) JUNCTION BOXES TO BE GROUNDED, 250-148. 3) SUPPORT M/C CABLE AS PER CODE 334-10 - WITHIN 12" AND EVERY 6' - OPEN UP SHELVE UNITS TO INSPECT CABLE SUPPORT. 4) FINISH MAKE-UP OF ELECTRIC AT JUNCTION BOXES. 5) SHEET METAL SCREWS ARE NOT ALLOWED FOR GROUNDING AT LIGHTS, 250-8. 6) PROPERLY SUPPORT CONDUIT - BLACK TAPE NOT APPROVED. 7) GROUND METAL HAUDE (?) FIXTURES. 8) SEPARATE ISOLATION GROUND AND GROUNDING EQUIPMENT CONDUCTOR THROUGHOUT RUNS AND AT BOXES. |