Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T03CM01879
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2004 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
01/21/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ DISCUSSED SECONDARY DRAIN PANS. OK TO PITCH FAN COIL ½" TOWARDS RETURN END OF UNIT. | |
01/16/2004 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ SECONDARY CONDENSATE DRAINS TO DISCHARGE INTO A CONSPICUOUS LOCATION. SECONDARY DRAIN PANS MUST EXTEND MIN. 1½" BEYOND ALL SIDES OF FAN COILS. PROVIDE ADEQUATE SERVICE CLEARANCE AT CONDENSORS. |