Permit: T03CM01879

Parcel: 14117005A


Addresses:

7451 S HOUGHTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T03CM01879

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/01/2004 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*
01/21/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ DISCUSSED SECONDARY DRAIN PANS. OK TO PITCH FAN COIL ½" TOWARDS RETURN END OF UNIT.
01/16/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ SECONDARY CONDENSATE DRAINS TO DISCHARGE INTO A CONSPICUOUS LOCATION. SECONDARY DRAIN PANS MUST EXTEND MIN. 1½" BEYOND ALL SIDES OF FAN COILS. PROVIDE ADEQUATE SERVICE CLEARANCE AT CONDENSORS.