Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 05/10/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Approved |
IVRS - Inspection :* |
| 04/14/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*/ 8" SDR 35 FROM MH 4 TO MH 5. 4 PSI AIR TEST OK AND TWO 4" FUTURE HCS CONNECTION STUBS AIR TEST OK. 6" SDR 35 FROM MH 5 TO C.O. 5, INCLUDING TWO 4" HCS ONE IS BLD ONE IS FUTURE. 4 PSI AIR TEST IS OK. |
| 04/13/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*/ VACUUM TEST MH. #4 AND MH #5 OK. |
| 04/08/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 04/07/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*/ FROM MANHOLE 5 TO 6" END OF LINE C.O. ON SOUTHWEST END OF ACE HARDWARE INCLUDING 4" FUTURE AND 4" STUB UP TO ACE HARDWARE AND TWO 4" STUBS TO SOUTH SHOWN PER PLAN. |
| 04/05/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*/ FROM MANHOLE #5 TO 100' EAST OK. |
| 04/02/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*/ FROM PUBLIC MANHOLE #4 270' TO EAST APP. 10' FROM MANHOLE # 5, 8" SDR 35 OK. 1) WILL NEED TO SEE AIRTEST AT LATER DATE. 2) NEED LETTER FROM ENGINEER STATING DESIRED PROFILE I.E. % OF FALL, CLEAN OUT ELEVATIONS, CERTIFICATION OF GRADE STAMPED FROM ENGINEER, DELETION OF CLEAN OUTS BETWEEN MANHOLE 4 AND 5. |
| 03/25/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*/ PROVIDE CITY APPROVED PLAN ON SITE. THIS IS A PRE-CON MTG. |
| 01/02/2004 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
IVRS - Inspection 0000*/ NORTH AND SOUTH EXTERIOR BLD SEWER FROM 2 - WAY CLEAN OUT - OUT 20' WEST WATER TEST OK. |