Permit: T03CM01879

Parcel: 14117005A


Addresses:

7451 S HOUGHTON RD


Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T03CM01879

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2004 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
04/14/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ 8" SDR 35 FROM MH 4 TO MH 5. 4 PSI AIR TEST OK AND TWO 4" FUTURE HCS CONNECTION STUBS AIR TEST OK. 6" SDR 35 FROM MH 5 TO C.O. 5, INCLUDING TWO 4" HCS ONE IS BLD ONE IS FUTURE. 4 PSI AIR TEST IS OK.
04/13/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ VACUUM TEST MH. #4 AND MH #5 OK.
04/08/2004 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection 0000*
04/07/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ FROM MANHOLE 5 TO 6" END OF LINE C.O. ON SOUTHWEST END OF ACE HARDWARE INCLUDING 4" FUTURE AND 4" STUB UP TO ACE HARDWARE AND TWO 4" STUBS TO SOUTH SHOWN PER PLAN.
04/05/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ FROM MANHOLE #5 TO 100' EAST OK.
04/02/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ FROM PUBLIC MANHOLE #4 270' TO EAST APP. 10' FROM MANHOLE # 5, 8" SDR 35 OK. 1) WILL NEED TO SEE AIRTEST AT LATER DATE. 2) NEED LETTER FROM ENGINEER STATING DESIRED PROFILE I.E. % OF FALL, CLEAN OUT ELEVATIONS, CERTIFICATION OF GRADE STAMPED FROM ENGINEER, DELETION OF CLEAN OUTS BETWEEN MANHOLE 4 AND 5.
03/25/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ PROVIDE CITY APPROVED PLAN ON SITE. THIS IS A PRE-CON MTG.
01/02/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*/ NORTH AND SOUTH EXTERIOR BLD SEWER FROM 2 - WAY CLEAN OUT - OUT 20' WEST WATER TEST OK.