Permit: T03CM01877

Parcel: 11618380A


Addresses:

1100 W FRESNO ST

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
04/13/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
1. 945-0529 CALL COULD NOT BE COMPLETED AS DIALED.
2. RPPBP INSTALLED OK
OK TO COVER
04/05/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1. RPPBP NOT INSTALLED PER PLAN.
2. WILL REQUIRE APPROVED DETAIL SHOWING TRANSITION FROM SCH 40 TO SCH 80 PVC TO COPPER ON THE VERTICAL RISER.
3. OK TO COVER
04/03/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1. PRESSURE TEST FROM WEST ISLAND TO METER OK
2. NEED TO SEE CONNECTIONS AT METER
3. NEED TO SEE ALL CONNECTIONS AT RPPBP
03/31/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
OK TO COVER 2" WATER LINE FROM METER TO RP LOCATION
RP NOT YET INSTALLED.
12/04/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :* AIR PRESSURE TEST IS OK
YARD WATER LINE IS STUBBED INTO WEST ISLAND ONLY.
SHALL SEE FINAL CONNECTION TO BACKFLOW PREVENTER.
11/23/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) SOIL WATER TEST IS OK
2) AIR PRESSURE TEST OF 65 POUNDS FOR YARD WATER LINE IS OK
3) NOTE: BLDG SEWER AND DOMESTIC WATER IS OK FROM BLDG TO WEST PARKING LOT AS INITALED ON APPROVED DRAWING
4) OK TO BACKFILL TRENCH