Permit: T03CM01872

Parcel: 141012030


Addresses:

5336 S CIVANO BL


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM01872

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
05/30/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK 2) HCS CONNECTION IS OK 3) OK TO BACKFILL TRENCH 4) YARD WATER LINE HAS A DRESSER COUPLING IN LINE THIS IS A REPAIR COUPLING AND NOT ACCEPTABLE ON A NEW INSTALLATION
05/29/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION
05/27/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) MUST PROVIDE APPROVED PLAN FOR EXCERCISE ROOM 2) MUST PROVIDE REVISED AND APPROVED PLAN FOR WASTE AND VENT SYSTEM FOR TOWNHOUSE B 3) PROVIDE A SEPARATE WATER TEST FOR 2ND FLOOR OR REMOVE FLAP AT BACKWATER VALVE 4) 1ST FLOOR BLDG DRAIN EXCEEDS 135 DEGREE CHANGE OF DIRECTION 5) YARD WATER LINE CALLS FOR 1 1/4" ALL THE WAY TO METER. DO NOT MIX MATCH MATERIALS