Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T03CM01872
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/30/2003 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK 2) HCS CONNECTION IS OK 3) OK TO BACKFILL TRENCH 4) YARD WATER LINE HAS A DRESSER COUPLING IN LINE THIS IS A REPAIR COUPLING AND NOT ACCEPTABLE ON A NEW INSTALLATION | |
05/29/2003 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION | |
05/27/2003 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*/ 1) MUST PROVIDE APPROVED PLAN FOR EXCERCISE ROOM 2) MUST PROVIDE REVISED AND APPROVED PLAN FOR WASTE AND VENT SYSTEM FOR TOWNHOUSE B 3) PROVIDE A SEPARATE WATER TEST FOR 2ND FLOOR OR REMOVE FLAP AT BACKWATER VALVE 4) 1ST FLOOR BLDG DRAIN EXCEEDS 135 DEGREE CHANGE OF DIRECTION 5) YARD WATER LINE CALLS FOR 1 1/4" ALL THE WAY TO METER. DO NOT MIX MATCH MATERIALS |