Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM01872
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
08/04/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK CEILING WALLS, BUILDER WILL HAVE LETTER FOR JERRY CONCERNING HEAT PUMPS | |
07/31/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) FEEDER CONDUIT MUST BE 2" AND AT LEAST 18" DEEP 2) ROOF HEAT PUMP CALLS FOR #4 AWG. PLEASE HAVE CHANGE ON APPROVED PLANS OR LETTER FROM ARCHITECT 3) STUB-OUTS IN BATHROOM MAY NEED A BOX UNLESS LISTED FOR OTHER | |
07/29/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) S.E. TYPE CABLE AND ROMEX NOT APPROVED FOR UNDERGROUND WET LOCATION. 2) NEED 3-'0'- TYPE BOXA FOR BOTH. ZOOM LIGHT? 3) WILL NEED APPROVAL ON DOWN SIZING OF S.E. CABLE FOR HEAT PUMP. |