Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/07/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/04/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK CEILING WALLS, BUILDER WILL HAVE LETTER FOR JERRY CONCERNING HEAT PUMPS |
| 07/31/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) FEEDER CONDUIT MUST BE 2" AND AT LEAST 18" DEEP 2) ROOF HEAT PUMP CALLS FOR #4 AWG. PLEASE HAVE CHANGE ON APPROVED PLANS OR LETTER FROM ARCHITECT 3) STUB-OUTS IN BATHROOM MAY NEED A BOX UNLESS LISTED FOR OTHER |
| 07/29/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) S.E. TYPE CABLE AND ROMEX NOT APPROVED FOR UNDERGROUND WET LOCATION. 2) NEED 3-'0'- TYPE BOXA FOR BOTH. ZOOM LIGHT? 3) WILL NEED APPROVAL ON DOWN SIZING OF S.E. CABLE FOR HEAT PUMP. |