Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2006 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 05/13/2005 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* 1) WAITING ON PAPERWORK FROM ARCHITECT. 2. FINISH FIRE WALL SEPARATION- BUILDING INSPECTOR TO APPROVE . OK WALLS SUBJECT TO PAPERWORK FROM ARCH. |
| 05/05/2005 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* NOT READY. 1) AN APPROVED FITTING IS NEEDED AT BOXES 370-17 AND PANELS. 2) SECURLY ATTACH CABLED CONNECTORS AT TOS OF PANEL CONNECTOR ONLY LISTED FOR 1-3 CABLES.4) TIGHTEN BOX CLAMPS AT ROUND BOXES. 5) SUPPORT NM CABLES WITHIN 12" OF CANS. 6) PLEASE MAKE UP ALL INTERIOR BOXES. 7) MAINTAIN FIREWALL SEPARATIONS AND PASS THRU'S. 8) PROTECT VDV CABLES FROM SHARP METAL EDGES AT TRUSSES & NM CABLES. 9) PLANS CALL FOR #6 WIRE ON 30 AMP CIRCUITS ALSO WHERE IS FEEDER CONDUCTOR SIZING. PLEASE PROVIDE A LETTER. NOTE: EXTERIRO BOXES MAY NEED APPROVED EXTENDER RINGS AT COMBUSTIBLES. |