Permit: T03CM01866

Parcel: 12213143C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/12/2006 ELECTRIC - INTERMEDIATE Approved
05/13/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) WAITING ON PAPERWORK FROM ARCHITECT. 2. FINISH FIRE WALL SEPARATION- BUILDING INSPECTOR TO APPROVE . OK WALLS SUBJECT TO PAPERWORK FROM ARCH.
05/05/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* NOT READY. 1) AN APPROVED FITTING IS NEEDED AT BOXES 370-17 AND PANELS. 2) SECURLY ATTACH CABLED CONNECTORS AT TOS OF PANEL CONNECTOR ONLY LISTED FOR 1-3 CABLES.4) TIGHTEN BOX CLAMPS AT ROUND BOXES. 5) SUPPORT NM CABLES WITHIN 12" OF CANS. 6) PLEASE MAKE UP ALL INTERIOR BOXES. 7) MAINTAIN FIREWALL SEPARATIONS AND PASS THRU'S. 8) PROTECT VDV CABLES FROM SHARP METAL EDGES AT TRUSSES & NM CABLES. 9) PLANS CALL FOR #6 WIRE ON 30 AMP CIRCUITS ALSO WHERE IS FEEDER CONDUCTOR SIZING. PLEASE PROVIDE A LETTER. NOTE: EXTERIRO BOXES MAY NEED APPROVED EXTENDER RINGS AT COMBUSTIBLES.