Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM01853
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/14/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* / 1) OK FINAL 2) SENT TO TEP ON 7/15AM | |
07/11/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ OK SERVICE CONDUCTORS TO PANEL. PLEASE PROVIDE A LADDER FOR INSPECTION ABOVE CEILING | |
06/27/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
06/26/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CANCELLED BY CONTRACTOR | |
06/24/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) FINISH ITEMS #1, 2, 3, & 6 OF PREVIOUS INSPECTION. 2) MAINTAIN WORKING CLEARANCE IN FRONT OF DISCONNECTING ??? 3) USE APPROVED U/C CONNECTORS NOT ROMEX CONNECTORS. 4) LABEL PANEL ON ?? 5) CONDUCTOR TO PANELS NOT AS PER PLANS-MISING 150 GROUND ALSO. 6) CANNOT USE OLD PANEL AS A JUNCTION BOX- USE AN APPROVED AND LISTED JUNCTION BOX. 7) WE HAVE OVER CONDUCTER FILL IN JUNCTION BOXES. 8) PULL BOX TO BE SIZED PER CODE. 9) CONDUCTORS IN CONDUIT TO BE AS PER CODE 310-3 |