Permit: T03CM01853

Parcel: 110113730

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM01853

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/14/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000* / 1) OK FINAL 2) SENT TO TEP ON 7/15AM
07/11/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ OK SERVICE CONDUCTORS TO PANEL. PLEASE PROVIDE A LADDER FOR INSPECTION ABOVE CEILING
06/27/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
06/26/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED BY CONTRACTOR
06/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) FINISH ITEMS #1, 2, 3, & 6 OF PREVIOUS INSPECTION. 2) MAINTAIN WORKING CLEARANCE IN FRONT OF DISCONNECTING ??? 3) USE APPROVED U/C CONNECTORS NOT ROMEX CONNECTORS. 4) LABEL PANEL ON ?? 5) CONDUCTOR TO PANELS NOT AS PER PLANS-MISING 150 GROUND ALSO. 6) CANNOT USE OLD PANEL AS A JUNCTION BOX- USE AN APPROVED AND LISTED JUNCTION BOX. 7) WE HAVE OVER CONDUCTER FILL IN JUNCTION BOXES. 8) PULL BOX TO BE SIZED PER CODE. 9) CONDUCTORS IN CONDUIT TO BE AS PER CODE 310-3