Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/14/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 07/11/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ PLEASE PROVIDE A LADDER FOR INSPECTION ABOVE CEILING. |
| 06/27/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FINISH ITEMS #2, 3, 4 AND 9 OF PREVIOUS INSPECTIONS 2) SHEET METAL NOT APPROVED FOR GROUNDING 250.8 3) OK TEMP C OF O |
| 06/26/2003 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 06/24/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*/ 1) APPROVED EXTENDER ARE NEEDED FOR MORE THAN 1/4" FROM BOX TO SURFACE 2) ELECTRICAL BOXES TO HAVE SUPPORT WIRES AND BE ATTACHED TO GRID AS PER 300.11 3) M/C CABLE AND FIXTURE WHIPS THAT ARE SUPPORTED TO BE AS PER 300.11 4) PROPERTY ATTACH FLEX TO CONNECTOR 5) M/C CABLE TO BE TERMINATED TO CONDUIT SYSTEM 6) WALK-IN BOX TO BE SEALED AT ENTRANCE TO BOXES 7) SUPPORT WIRES ON ALL FIXTURES AND ATTACH TO GRID |
| 06/20/2003 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* 1) PLEASE MAKE ALL CORRECTIONS ON PREVIOUS INSPECTIONS BEFORE PROCEEDING. 2) COPPER PIPE HANGERS NOT APPROVED 3) EXPANSION TANK NOT SUPPORTED . INSPECTION STOPPED. |