Permit: T03CM01837

Parcel: 12902084B


Addresses:

2644 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM01837

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
05/28/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
05/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS EXCEPT PATIENT CARE ROOMS THESE ROOM TO BE INSTALLED AS PER ART 517.3 INCLUDING EXISTING OUTLETS NM CABLE PER LETTER FROM ENGINEER SEE ATTACHED.
05/15/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
05/14/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*A LETTER AUTURIZING USE OF NM CABLE FROM THE ENGINEER IS NEEDED.
2.) SUPPORT BOXES FROM BAC MOVEMENT PER SPEC #10F.
3.) PLEASE VERIFY IF EXAM ROOM FALL UNDER PATIENT CARE AREAS OF 517.