Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/08/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ OK FOR C OF O.
10/03/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 3/8" ID GAS FLEX CONNECTORS STILL HAVE NOT BEEN CHANGED. 3/8" ID GAS FLEX IS NOT ADEQUATE FOR150,000 BTU. SEE THE LISTING SUPPLIED WITH FLEX CONNECTOR.