Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM01829
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2003 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 05/21/2003 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0999*REMOVE CEILING TILES TO EXPOSE MECHANICAL SYSTEM FOR INSPECTION. RECALL FOR INSPECTION. | |
| 05/19/2003 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0999* | |
| 05/14/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*CONDENSATE DRAIN LINE DOES NOT HAVE ADEQUATE SLOPE. PROVIDE MIN 1/8" PER FT SLOPE. FINISHING INSTALLING TO MOP SINK. RECALL FOR INSPECTION. |