Permit: T03CM01827

Parcel: 11004345C


Addresses:

3215 N SWAN RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM01827

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/10/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK SEAL OFFS 2) OK FOR FUEL TO PUMPS
11/07/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK CARWASH AND VACCUM EQUIPMENT FOR LISTINGS 2) FINISH CANOPY WIRING AND CONDUITS 2) NEW CHICO SEAL IS UL LISTED-OK TO USE
11/05/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) PLEASE VERIFY LABELING AND LISTING OF NEW CHICO SEAL BEFORE USAGE 2) OK LAST 5' OF CONDUITS TO POOL BOXES
10/30/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK TO RE-ASPHALT PARKING LOT, OK PHONE PEDISTAL POWER 2) ONLY ONE CONDUIT IS IN USE UNDER PARKING/DRIVE AREA FOR POWER OTHER THAN PUMPS. IT IS PASSING THROUGH CLASS I DIV II AREA. WE WILL NEED RIGID CONDUIT TO THE LAST 24" TO EMERGANCE AND SEAL OFF. MAINTAIN 18" OF COVER FOR NEW CONDUITS IN PLATER AREAS 3) CONDUITS UNDER CAR WASH DRIVE THRU TO BE AT 24" OR 2" OF CONCTRETE ENCASEMENT FULL CIRCUMFERANCE 4) FINISH RUNS TO NEW PULL BOX AND NEW CONDUIT RINS FOR LIGHTING
09/30/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) JUNCTION BOXES TO BE ACCESSIBLE 2) M/C CABLE TO BE SUPPORTED WITHIN 12" OF BOXES
09/23/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS AND HARD CEILING EXCEPT AS NOTED: NO MORE THAN 360 DEGREE IN A CONDUIT RUN
08/19/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*