Permit: T03CM01827

Parcel: 11004345C


Addresses:

3215 N SWAN RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T03CM01827

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2003 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*
11/05/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*
11/01/2003 ELECTRIC - UNDERGROUND Partial Approval 1) OK TO POUR CONCRETE FOR ENCASEMENT IN CAR WASH DRIVE THRU 2) PLEASE VERIFY LISTING LABELS FOR: CAPPUCCINO MACHINE, TEA MACHINE, SODA MACHINE AND ICE MACHINE 3) EXTENDER RING NOT TO BE METAL-USE APPROVED LISTED RINGS 3) INSTALL SATELITE GROUNDING CONDUCTOR AS PER 810.21
10/31/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK TO WITHIN 5' OF PULL BOXES IN PLANTERS 2) CAR WASH AREA HAS A BROKEN CONDUIT-PLEASE REPAIR
10/22/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* OK 5 POLE BASES
10/07/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) CONDUITS TO BE BURIED AS PER CODE 300.5 2) 60' PLUS OF CONDUIT COVERED WITHOUT INSPECTION-UNDER 6" OF REINFORCED CONCRETE, NO ENCASEMENT 3) OK 3 POLE BASES ON SOUTH AND EAST EDGE
09/19/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK TO COVER AS DISCUSSED 2) OK CONDUITS ON TOP OF TANKS 3) OK CONDUITS IN RUNS BETWEED DISPENSERS 4) NO MORE THAN 360 DEGREE IN A RUN. WE HAVE 350-360 DEGREE AT TURN TO DISPENSER 5) FINISH RUNS
09/16/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) ITEM #2 DATED 8/4/03, NO MORE THAN 360 DEGREE IN A RUN 2) PLEASE PROVIDE SPECS AND INSTRUCTIONS FOR RECOATING PVC COATED CONDUIT 3) INSTALL PVC FITTINGS CORRECTLY
08/27/2003 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0920*/ NO ACCESS DUE TO ROAD CLOSURES.
08/19/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK 4-FLOOR BOXES AND CONDUIT
08/15/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ ALL INSIDE BLDG OK EXCEPT FLOOR BOXES.
08/04/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK 30' OUT FROM BLDG (34 CONDUITS) 2) NO MORE THAN 360 DEGREE IN A RUN
07/31/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) OK 3-4" PRIMARS, OK 1-3" PVC, OK 3-2 1/2" PVC, OK 1-1 1/2" PVC (UNDERSLAB) 2) OK 23-RIGID STUD INTO BUILD-WE HAVE 180 DEGREE IN RUN AT THIS TIME