Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/22/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 07/15/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1) SHORT RADIOUS 90 NOT ALLOW IN HORIZONTAL DRAIN. 2) SANITARY & FITTINGS NOT ALLOWED IN HORIZONTAL DRAIN 3) SEWER DRAINS CANNOT RUN IN OR PARALLEL TO FOOTING WITHIN 2 FEET OF FOOTING 4) TOILET NOT VENTED 5) PVC WATER CANNOT RUN IN FOOTING 6) PROVIDE 10 FEET HIGH WATER TEST PER U.P.C SECTION 710.2 7) EXCESS OF 135 DEGREE HORIZONTAL DIRECTION CHANGE REQUIRES CLEAN ON ??. 8) 2 WAY CLEAN OUT REQUIRED FOR ADDITION |