Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM01801

Parcel: 13225047B


Addresses:

4790 S JULIAN AV


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T03CM01801

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2003 ELECTRIC - UFER Approved IVRS - Inspection 0000*/ 1) GROUND RING APPROVED 2) NEED ROD CONNECTIONS AND RODS
06/26/2003 ELECTRIC - UFER Denied IVRS - Inspection 0999*/ 1) PLEASE HAVE GROUND RING PROPERLY POSITIONED AT 2 1/2 FEET DEPP WITHOUT LOOPS GOING UP 2) FASTEN GROUNDING WIRE AT TRENCH IF NECESSARY
06/12/2003 ELECTRIC - UFER Denied IVRS - Inspection 0245*/ 1) NOT APPROVED. MEET BE PER PLAN (GROUND RING)