Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM01793
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
10/03/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) PERMANENTLY LABEL BOTH A-C UNITS AND DISCONNECT AT ROOF TOP SERVICE AREA 2) MAKE HIGH LEG WITH ORNAGE TAPE AND MUST BE ON 'B' PHASE OF LINE SIDE DISCONNECT 3) LABEL A/C DISCONNECT EG. A/C1, A/C2 FEEDER 4) NEED A NEUTRAL TO NEW 100 AMP DISCONNECT 5) A NEUTRAL IS REQUIRED PER 250.24 6) ALSO A NEUTRAL DISCONNECT LINK FOR THE TERMINATION IS REQUIRED IN DISCONNECT FOR NEUTRAL | |
10/02/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
09/30/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*/ 1) NO ACCESS, PLEASE RECALL | |
06/16/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) BELOW TI 2) ROOF TOP EQUIPMENT RECLACED, NEW ETC. 3) WILL NEED CITY APPROVED ACCURATE PLAN OF ALL ROOF TOP EQUIPMENT PERTAINING TO THIS OCCUPANCY (PERMIT) | |
06/12/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) INSTALL ALL SCREWS IN INDUSTRIAL RAISED COVERS 2) NEED DISCONNECT FOR WATER HEATER 3) NEED TO SEE A/C |