Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/07/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/03/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PERMANENTLY LABEL BOTH A-C UNITS AND DISCONNECT AT ROOF TOP SERVICE AREA 2) MAKE HIGH LEG WITH ORNAGE TAPE AND MUST BE ON 'B' PHASE OF LINE SIDE DISCONNECT 3) LABEL A/C DISCONNECT EG. A/C1, A/C2 FEEDER 4) NEED A NEUTRAL TO NEW 100 AMP DISCONNECT 5) A NEUTRAL IS REQUIRED PER 250.24 6) ALSO A NEUTRAL DISCONNECT LINK FOR THE TERMINATION IS REQUIRED IN DISCONNECT FOR NEUTRAL |
| 10/02/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 09/30/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920*/ 1) NO ACCESS, PLEASE RECALL |
| 06/16/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) BELOW TI 2) ROOF TOP EQUIPMENT RECLACED, NEW ETC. 3) WILL NEED CITY APPROVED ACCURATE PLAN OF ALL ROOF TOP EQUIPMENT PERTAINING TO THIS OCCUPANCY (PERMIT) |
| 06/12/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) INSTALL ALL SCREWS IN INDUSTRIAL RAISED COVERS 2) NEED DISCONNECT FOR WATER HEATER 3) NEED TO SEE A/C |