Permit: T03CM01759

Parcel: 14113837B


Addresses:

8045 S RITA RD #175

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/29/2003 ELECTRIC - INTERMEDIATE Approved
04/23/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*WALK APPROVED.
NEED FULL TAG ON A.C. CABLE USED. OK TO COVER SUBJECT TO HAVING APPROVED GRADE A C.CABLE NEED LETTER FROM ENGINEER AN THE USEAGE OF A.C. CABLE.
04/22/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
04/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*M.C. CABLE NOT ON PLAN
2.) NOT READY.
3.) SEE NOTES WILL NEED TO USE PROPER WIRING METHODS AND MATERIAL
4.) COMPLY W/ART. 517.
5.) COLOR CODE BRANCH CIRCUITS.
6.) 2 SEPARATE SERVICE AND HALVER AT ONE AREA CIRCUITS ARE COMBINED.