Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/03/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 08/28/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ CANCELLED BY DAVE. |
| 08/27/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANCELLED BY CONTRACTOR |
| 08/01/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) INSTALL SERVICE DOES NOT REFLECT PLANS AT SITE. WHERE ARE ADDITIONAL BREAKERS AND DEVICES. PLANS CALL FOR 80/3 WE HAVE 70/3 WHAT ABOUT LOCATION |
| 07/30/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) MAIN BONDING JUMPER TO BE SIZED PER 250-66 2) PLEASE PROVIDE REJ?? PINS 3) IF GAS PIPING IS INSTALLED THE PIPING WILL NEED TO BE BONDED 250-104 4) SUPPORT SEAL TITE TO UNIT AS PER CODE 5) LABELLING TO BE PERMANENT 110.22 6) TIGHTEN LOOSE FITTINGS 7) SERVICE EQUIPMENT TO BE MOUNTED WITH 1/4" MINIMUN HARDWARE NOT DRYWALL SCREWS 8) PLANS SHOW SERVICE IN A DIFFERENT LOCATION -ALSO WHERE IS 1-LINE DIAGRAM |