Permit: T03CM01748

Parcel: 12501010B


Addresses:

2618 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK FINAL
08/28/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ CANCELLED BY DAVE.
08/27/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED BY CONTRACTOR
08/01/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) INSTALL SERVICE DOES NOT REFLECT PLANS AT SITE. WHERE ARE ADDITIONAL BREAKERS AND DEVICES. PLANS CALL FOR 80/3 WE HAVE 70/3 WHAT ABOUT LOCATION
07/30/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999* 1) MAIN BONDING JUMPER TO BE SIZED PER 250-66 2) PLEASE PROVIDE REJ?? PINS 3) IF GAS PIPING IS INSTALLED THE PIPING WILL NEED TO BE BONDED 250-104 4) SUPPORT SEAL TITE TO UNIT AS PER CODE 5) LABELLING TO BE PERMANENT 110.22 6) TIGHTEN LOOSE FITTINGS 7) SERVICE EQUIPMENT TO BE MOUNTED WITH 1/4" MINIMUN HARDWARE NOT DRYWALL SCREWS 8) PLANS SHOW SERVICE IN A DIFFERENT LOCATION -ALSO WHERE IS 1-LINE DIAGRAM