Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2003 | FIRE - KITCHEN EXH HOOD FINAL | Approved | IVRS - Inspection 0000* | |
| 05/02/2003 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. Needs 12 yr. hydrostatic test of extinguishing agent cylinder. 2. Needs automatic gas shut-off valve. 3. Extinguishing agent nozzles need to be repositioned over cooking appliances. |