Inspection History: BUILDING PRE-SLAB
Permit Number - T03CM01735
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2003 | BUILDING PRE-SLAB | Approved | IVRS - Inspection 0000* | |
04/25/2003 | BUILDING PRE-SLAB | Partial Approval | IVRS - Inspection 0000*/ 1) YOU MUST REVISE THE PLAN AND PERMIT TO RELOCATE ELECTRIC SERVICE AND GAS LINE 2) GAS LINE NOT ALLOWED UNDER COVERED SLAB 3) ELECTRIC SERVICE CANNOT BE ENCLOSED IN HOUSE 4) UNDER GROUND ELECTRIC WIRE ON SOUTH WALL MUST BE 24" BELOW GRADE. CANNOT BE ENCASED IN CONCRETE FOOTER 5) IF YOU ARE RELOCATING ELECTRIC SERVICE THEN YOU SHOULD ATTACH A UFER GROUND TO REINFORCING STEEL |