Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM01717
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*OK FOR C OF O. | |
05/21/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1.) STRAPS ON FLEX DUCT MUST BE SPACED NO MORE THAN 5' ALSO MAINTAIN MIN. 1 1/2" WIDE BANDING ON FLEX DUCT. INSULATE SPIRAL DUCT ABOVE CEILING. 2.) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PROVIDE MIN 1/8" PER FT. SLOPE. |