Permit: T03CM01717

Parcel: 13312006M

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM01717

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
05/21/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) STRAPS ON FLEX DUCT MUST BE SPACED NO MORE THAN 5' ALSO MAINTAIN MIN. 1 1/2" WIDE BANDING ON FLEX DUCT. INSULATE SPIRAL DUCT ABOVE CEILING.
2.) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. PROVIDE MIN 1/8" PER FT. SLOPE.