Permit: T03CM01707

Parcel: 134082920

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
08/27/2003 SHEET ROCK NAILING Approved IVRS - Inspection 0000*
07/08/2003 SHEET ROCK NAILING Partial Approval IVRS - Inspection 0000* 1) FIRE RATED WALL REQUIRES NAILS/SCREWS @ 8" OC ALONG TOP, BOTTOM AND EDGES OF ROCK. 2) FIRE RATED WALLS REQUIRE TIGHT CONSTRUCTION @ SHEET ROCK JOINTS ( ICBO IDENTIFIES TIGHT AS 1/16'' GAP MAX) 3) (SCRATCHED OUT) 4) OK TO TAPE WHEN LARGE ?? CAULKED WITH FIRE SEAL