Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM01662

Parcel: 117120060


Addresses:

54 E PENNINGTON ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM01662

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/24/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK. 2) OK FOR C OF O PENDING ANY OTHER INSP. 3) LAST INSPECTOR TO LEACE GAS CARD.
11/17/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) USE APPROVED DRAINAGE MATERIAL AT PEPSI MACHINE. 2) INSTALL ANSUL VALVE SO THAT IT IS ACCESSABLE. UNIONS ARE NOT PERMITTED ABOVE T-BAR. 3) SUPPORT MIXING VALVES. 4) CAULK ALL FIXTURES. 5) BACKFLOW CERTS.
11/06/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) PLEASE MAKE ALL CORRECTIONS AND HOOK UP ALL DRAINS BEFORE CALLING FINAL. PLEASE HAVE CERTIFICATIONS FOR BACKFLOW DEVICES.
10/27/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) MUST HARD PIPE STOCK POT #25 GAS PIPE OR PROVIDE QUICK DISCONNECTS WITH SAFETY CABLES 2) CAN ONLY HAVE ONE SLIP JOINT ON TRAP ARM FOR DISHWASHER SINK 3) TRIPLE COMPT SINK TRAP ARM EXCEEDS 135 DEGREE CLEANOUT REQUIRED