Permit: T03CM01662

Parcel: 117120060


Addresses:

54 E PENNINGTON ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T03CM01662

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2003 PLUMBING - INTERMEDIATE Approved 1) ABS DWV THRU ROOF OK WATER TEST OK. 2) COPPER OVERHEAD AND IN THE WALLS OK PRESSURE TEST OK. 3) NEED TO SEE COPPER IN MECH ROOM. 4) NEED TO SEE CLOSET FLANGES. 5) OK TO COVER.
06/24/2003 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* 1) NOT READY FOR INSPECTION. 2) GAS PIPING IN THE WALL FOR KITCHEN EQUIPMENT UP TO ANSAL VALVE OK. PROESSURE TEST OK. OK TO COVER.
06/22/2003 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* 1) NO WATER TEST ON ABS. 2) NO PRESSURE TEST ON WATER.