Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T03CM01662
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
10/10/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) KITCHEN CEILING MAY BE COMPLETED |