Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/30/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 05/21/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) CONDENSATE NOT COMPLETE 2) MISSION CAP NOT ALLOWED IN WALL CAVITY. USE PERM CAP 3) NO DWV WATER TEST PER UPC 712.2 4) VENT FITTING IN HORIZONTAL VENT AT KITCHEN BELOW 6" ABOVE FLOOD RIM MUST BE APPROVED DRAIN FITTINGS 5) FIRE BLOCK MISSING KITCHEN 6) 3 POINT BEARING TRUSSES NOT BEARING MASTER BEDROOM 7) REVISE PLAN FOR ADDRESS 8) NAIL PROTECT PEX AT MASTER BEDROOM FURR OUT 9) FIRE BLOCK BEDROOM 3 SOUTH WALL 10) BLOCK SHEAR WALL PENETRATIONS 4 SIDES AND NAIL PER PLAN 11) STOPPED INSPECTION. TOO MANY ITEMS |