Permit: T03CM01645

Parcel: 128100800

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T03CM01645

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/21/2003 MECHANICAL - ABOVE CEILING Approved
06/20/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000* 1) PROVIDE SUPPORTS ON GREASE DUCT. 2) INSTALL ACCESS PANELS. BOND ANY LOOSE WRAP. NEED TO SEE WRAP EXTEND TO TOP OF CURB WILL CHECK ON LATER INSPECTION. 3) PROVIDE INSTALLATION INSTRUCTIONS FOR ACCESS DOOR.
06/11/2003 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) NEED TO SEE BATHROOM EXHAUST 2) DUCT SMOKE DETECTORS TO BE INSTALLED IN RETURN PLENIUMS 3) PROVIDE SECONDARY DRAINS ON AIR HANDLERS 4) OK TO PROCEED WITH FIRE WRAP AND CLEANOUTS 5) OK FOR SHEET ROCK NOTE: SECONDARY DRAIN PAN WITH OVERFLOW SENSOR WOULD BE ACCEPTABLE