Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T03CM01645
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2003 | MECHANICAL - ABOVE CEILING | Approved | ||
06/20/2003 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* 1) PROVIDE SUPPORTS ON GREASE DUCT. 2) INSTALL ACCESS PANELS. BOND ANY LOOSE WRAP. NEED TO SEE WRAP EXTEND TO TOP OF CURB WILL CHECK ON LATER INSPECTION. 3) PROVIDE INSTALLATION INSTRUCTIONS FOR ACCESS DOOR. | |
06/11/2003 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NEED TO SEE BATHROOM EXHAUST 2) DUCT SMOKE DETECTORS TO BE INSTALLED IN RETURN PLENIUMS 3) PROVIDE SECONDARY DRAINS ON AIR HANDLERS 4) OK TO PROCEED WITH FIRE WRAP AND CLEANOUTS 5) OK FOR SHEET ROCK NOTE: SECONDARY DRAIN PAN WITH OVERFLOW SENSOR WOULD BE ACCEPTABLE |