Inspection History: PLUMBING - FINAL

Permit Number - T03CM01645

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/25/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) PLBG FINAL IS OK 2) OK FOR C OF O
06/24/2003 PLUMBING - FINAL Denied 1) MUST COMPLETE CONNECTION TO GAS LINE TO ALL APPLIANCES 2) MUST REMOVE UNIONS IN T-BAR CEILING SEE SECTION 1211.10 INTERPRETATION 94UPC. 3) MUST USE DRECTIONAL FITTINGS FOR CONTINUOUS WASTE SEE SECTION 405.4 94UPC 4) CAN ONLY HAVE (1) SCIP JOINT ON OUTLET SIDE OF TE?? SEE SECTION1003.3 94UPC 5) ICE MACHINE REQUIRES BACKFLOW PREVENTER 007 TESTED & CERTIFIED BY TIMEOF INSPECTION. 6) MUST PROVIDE A HANGER DOWNSTREAM OF WATER METER AND USE COPER HANGERS. 7) OK FOR GRID TILE.