Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM01645
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) PLBG FINAL IS OK 2) OK FOR C OF O | |
06/24/2003 | PLUMBING - FINAL | Denied | 1) MUST COMPLETE CONNECTION TO GAS LINE TO ALL APPLIANCES 2) MUST REMOVE UNIONS IN T-BAR CEILING SEE SECTION 1211.10 INTERPRETATION 94UPC. 3) MUST USE DRECTIONAL FITTINGS FOR CONTINUOUS WASTE SEE SECTION 405.4 94UPC 4) CAN ONLY HAVE (1) SCIP JOINT ON OUTLET SIDE OF TE?? SEE SECTION1003.3 94UPC 5) ICE MACHINE REQUIRES BACKFLOW PREVENTER 007 TESTED & CERTIFIED BY TIMEOF INSPECTION. 6) MUST PROVIDE A HANGER DOWNSTREAM OF WATER METER AND USE COPER HANGERS. 7) OK FOR GRID TILE. |