Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM01642

Parcel: 136326360

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
04/06/2004 ROOF NAILING Approved IVRS - Inspection 0000*
03/31/2004 ROOF NAILING Not ready for Inspection IVRS - Inspection 0000*/ 1) MISSING RAFTER HANGERS AT LEDGERS, THRU OUT 2) VIGA LOGS AT BEARING ENDS WERE NOT INSTALLED PER PLAN, HAVE SLOT IN ENDS APPROVED 3) SEE RED MARKS ON ROOF DECK, MISSED NAILING AND H2.5 4) NAIL ITT.211.88-10D'S REQUIRED 83 SIMPSON 5) HEADER SIZE LIVING H-5 3-2 X 12 FLITCH BEAM-WRONG SIZE INSTALLED 6) H-6 HEADER FOYER, WRONG SIZE INSTALLED 7) H-5 HEADERS DELETED FRONT BATH, MISSING TJ HANGERS 8) CAN'T SEE A.35 AT 1/S4 ENTRY 9) NEED BEARING HEADER END, FOYER VIGA POST OTHER SIDE H-3 HEADER 10) NEED FULL BEARING UNDER 6 X 10 LIVING ROOM EXT. WALL 11) GAME ROOM, WINDOW REMOVED-NOT INSTALLED 12) COLUMN BASES NOT INSTALLED PER PLAN 13) NEED A CROSS SECTION OF DINING ROOM TO GREAT ROOM WALL