Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/04/2003 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 07/30/2003 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*/ NOTES: 1) SUPPORT CONDUIT WITHIN 3' AT TERMINATIONS, AND 10' INTERVALS. PER ART 348 NEC 2) MC CABLE MUST BE SUPPORTED WITHIN 12" EACH TERMINATION AND 6' INTERVALS, EXCEPTION FOR FIXTURE WHIPS NOT EXCEEDING 6' IN LENGTH PER 334 NEC 3) PENDANT HUNG LIGHT FIXTRUES NEED SUPPORT IN ADDITION TO CEILING GRID PER ART 300 NEC #9287 CITY OF TUCSON ORDINANCE 4) COMPLETE INSTALL AND MAKE-UP OF FIXTURES |