Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM01617
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1) SOIL WATER TEST IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) OL FOR DRYWALL. | |
06/19/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) MUST STRAP DOWN DOMESTIC WATER LOTS OF LOOSE PIPES AND ?? 2) COPPER H. W. IS TOUCHING CARRIER. 3) SOIL WATE R TEST IS OK. 4) MUST PROVIDE A HANGER ON HORIZONTAL VENTS WITHIN 18" OF COUPLINGS | |